SIGFLOW FILTERS

Maintenance:
The maintenance interval depends on local atmospheric contamination. The differential pressure gauge gives a constant indication of the filter condition, and if left unattended the differential pressure will rise to xxxx mmwg. The pressure switch will then trip, and the alarm will be sound (if connected).
Cleaning:
The polyester filter cartridges can be cleaned and reused a number of times.
The motor must be stopped when cleaning the filter elements
Remove the filter elements from the dust collector. The filter element can be cleaned using a water jet.

  1. Before cleaning each element, it should be inspected thoroughly to check for damage to the filter media or metal / plastic parts. If any damage has occurred, the cartridges must be disposed of and replaced.
  2. Use a high-pressure water jet (maximum pressure 50 bar), standing at a distance of at least 50cm from the element concerned
  3. A sulphur free detergent may be used if necessary.
  4. Allow the filter to dry thoroughly
  5. Re-inspect the filter cartridges to ensure that no damage has occurred during the washing process, and check the filter media for signs of wear and ageing. Replace any cartridges which show signs of media weakness or damage to the metal parts.

A reading should be taken from the pressure differential gauge both before and after each cleaning process. If cleaning has been carried out correctly, the gauge will register a lower reading after cleaning.